BA 138R/09/en/08.04No.: 51006049Operating InstructionsSafety Data Manager (SDM)Memo-Graph SSystem compatible data manager with a unique safety concept
2 Identification Memo-Graph S10 Endress+Hauser2.1.2 Product structureSafety Data ManagerInputs/outputs on slot 1A Slot 1 not usedB 8 Multifunction inp
Memo-Graph S 3 InstallationEndress+Hauser 112.2 Scope of delivery• Device (with screw plug-in terminals for mains and signal connection, according to
3 Installation Memo-Graph S12 Endress+Hauser3.3 Installation instructions3.3.1 Mounting kitTo install the control panel, all you need is a screwdriver
Memo-Graph S 4 WiringEndress+Hauser 134 Wiring4.1 Quick wiring guide"Caution!Before wiring, please compare the supply voltage with the informatio
4 Wiring Memo-Graph S14 Endress+HauserFigure 3: Connections/terminal diagramRxD/TxD(-)RxD/TxD(+)screenPin8532housingRS 232GNDRxDTxDEthernetRS 232RS 42
Memo-Graph S 4 WiringEndress+Hauser 15"Caution!Depending on the order, slots 1 or 2 can be fitted with different boards (with analogue and/or dig
4 Wiring Memo-Graph S16 Endress+HauserOptional open collector output* (NPN Transistor):98 Collector99 Emitter!Note!The opening and closing function (=
Memo-Graph S 4 WiringEndress+Hauser 174.2.3 Multifunction output board with relay (slot 2)Analogue outputs:The first digit (x) of the three-digit term
4 Wiring Memo-Graph S18 Endress+Hauser!Note!The opening and closing function (= activation and deactivation of the relay coil) in case of a limit valu
Memo-Graph S 4 WiringEndress+Hauser 19Relay outputs* on digital board(s):!Note!The opening and closing function (= activation and deactivation of the
Memo-Graph S2 Endress+HauserOverviewYour new Safety Data Manager (SDM) has the Operating Instructions built-in.The device's simple control system
4 Wiring Memo-Graph S20 Endress+HauserOptional interface: alternatively RS 485 or Profibus DP (bus monitor)4.2.6 Front-mounted RS 232 interface* (jack
Memo-Graph S 4 WiringEndress+Hauser 214.3 Connecting a device to the Ethernet (TCP/IP)In principle, all devices equipped with an internal Ethernet int
4 Wiring Memo-Graph S22 Endress+Hauser4.3.2 Operating locationThe operating location of the device should be selected such that the network-specific m
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 235 Operation / adjusting device settings - Set-up to com
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S24 Endress+Hauser5.4 Beginning device configuration - Set-up (when unlo-
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 25The main menu:!Note!If individual chapters are missing,
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S26 Endress+HauserInput principle:1. Begin changing each parameter with “
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 275.6 Set-up using ATA flash cardSave the device settings
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S28 Endress+HauserBasic settings: Operating modes sub-menuSettings that d
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 29Basic settings -> Operating modes: Recalibration sub
Memo-Graph S CHANGE PROTOCOLEndress+Hauser 3CHANGE PROTOCOLDOCUMENT REVISION HISTORYDocument revision number 1.3, Stand 24.08.2004Safety Data Manager
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S30 Endress+HauserBasic settings: ATA flash change sub-menuSettings that
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 315.7.2 Signal settingsSettings, groupings and combinatio
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S32 Endress+HauserSignal settings -> Analogue inputs -> Analogue in
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 33Signal settings -> Analogue inputs -> Analogue in
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S34 Endress+HauserIn the analogue inputs / signal menu the “from data int
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 35Signal settings: Digital inputs sub-menu (Option):!Note
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S36 Endress+HauserSet-up -> Signal settings -> Digital inputs ->
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 37Effect of the control input Only when used as control i
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S38 Endress+HauserOnly when using the digital input as impulse counter Co
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 39Signal settings -> Digital inputs: Limit values sub-
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S40 Endress+HauserOnly when using the digital input as on/off events func
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 41Detailed settings in the set-up under Signal settings -
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S42 Endress+HauserSignal settings: Digital combinations sub-menuSettings
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 43Set-up -> Signal settings -> Digital combinations
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S44 Endress+HauserDescription “H” Description of the status when the comb
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 45Signal settings: Analogue outputs (option) sub-menuSett
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S46 Endress+HauserSignal settings: Signal groups sub-menuOnly channels th
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 475.7.3 Signal analysisSettings only required if the inpu
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S48 Endress+Hauser5.7.4 ProductsHere, the settings for 20 different produ
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 49Products: Product x sub-menuViewing or changing setting
Memo-Graph S Table of contents5Table of contentsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Brief overview . . . . . . . . . .
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S50 Endress+Hauser5.7.5 Texts40 different texts (22 characters) can be en
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 51Administration: Create ID sub-menu5.7.7 InterfacesInfor
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S52 Endress+HauserInterfaces: RS232 / RS422 / RS485 sub-menuSettings only
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 53Interfaces: Data interface (option) sub-menuSelecting t
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S54 Endress+HauserService: General sub-menuInformation for service techni
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 55Service: Calibration sub-menuFactory calibration for cl
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S56 Endress+Hauser5.9 Communication via serial interfaces / modem5.9.1 RS
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 575.9.4 Commissioning a modem linkIn principle, any conve
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S58 Endress+Hauser!Note!You can obtain the system parameters from your re
Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioningEndress+Hauser 59Please be aware that this number is not arbitrary, rath
Table of contents Memo-Graph S68 Accessories . . . . . . . . . . . . . . . . . . . . 789 Trouble-shooting . . . . . . . . . . . . . . . . 799.1 Re
5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S60 Endress+Hauser3. Now enter the IP address. The port address is 8000.E
Memo-Graph S 6 Guaranteeing the requirements of 21 CFR 11Endress+Hauser 616 Guaranteeing the requirements of 21 CFR 116.1 GeneralPrior to introducing
6 Guaranteeing the requirements of 21 CFR 11 Memo-Graph S62 Endress+Hauser6.2 Important settings at the device6.2.1 Basic settings/operating modes• AT
Memo-Graph S 6 Guaranteeing the requirements of 21 CFR 11Endress+Hauser 636.2.3 AdministrationSet the password length and validity period etc. in acco
6 Guaranteeing the requirements of 21 CFR 11 Memo-Graph S64 Endress+Hauser6.2.5 Analogue inputs• Select the number of decimal places to suit the measu
Memo-Graph S 6 Guaranteeing the requirements of 21 CFR 11Endress+Hauser 656.3.2 Activating the automatic read-out function and autom. data sto-rageA r
6 Guaranteeing the requirements of 21 CFR 11 Memo-Graph S66 Endress+Hauser6.3.4 Activating automatic batch print-outA reliable, fully functional inter
Memo-Graph S 6 Guaranteeing the requirements of 21 CFR 11Endress+Hauser 67
6 Guaranteeing the requirements of 21 CFR 11 Memo-Graph S68 Endress+Hauser
Memo-Graph S 7 Procedure in operationEndress+Hauser 697 Procedure in operationVersion with die-cast front : Version with stainless steel front:Figure
Memo-Graph S 1 Safety instructionsEndress+Hauser 71 Safety instructions1.1 Notes on safety conventions and iconsThe devices are safely built and teste
7 Procedure in operation Memo-Graph S70 Endress+HauserFunctions of the LEDs“NamurNE44” setting (see “Set-up”):- Green LED lights up: power supply OK-
Memo-Graph S 7 Procedure in operationEndress+Hauser 71Checking product limit values:Product - InformationProduct - Carrying out recalibration:Product
7 Procedure in operation Memo-Graph S72 Endress+HauserSaving device settings / saving onto ATA flash card:Extras - ATAFlash - Save set-up to ATAFlashR
Memo-Graph S 7 Procedure in operationEndress+Hauser 73• The user who presently has responsibility is displayed in normal operation in the screen'
7 Procedure in operation Memo-Graph S74 Endress+Hauser7.2.3 Enter comment / textThe device can save pre-definable or free texts together with the auto
Memo-Graph S 7 Procedure in operationEndress+Hauser 75Group displaySelect how the currently-selected group is to be displayed: • Plot - time axis is p
7 Procedure in operation Memo-Graph S76 Endress+HauserSearchThe ring memory can be searched through according to different search criteria. The result
Memo-Graph S 7 Procedure in operationEndress+Hauser 77The following functions are available:• Update ATA flash: closes the current block in the memory
8 Accessories Memo-Graph S78 Endress+Hauser8AccessoriesAccessories included in delivery see Chapter 2.2Designation Order codeEthernet module, RS 232,
Memo-Graph S 9 Trouble-shootingEndress+Hauser 799 Trouble-shooting9.1 Response of device to faultsYour Safety Data Manager informs you of faults or in
1 Safety instructions Memo-Graph S8 Endress+Hauser1.4 Operational safety"Caution!Operation is only guaranteed as safe when the instructions and w
9 Trouble-shooting Memo-Graph S80 Endress+Hauser9.3 Searching for and eliminating faultsProblem Cause RemedyAnalogue input shows “---” The signal line
Memo-Graph S 9 Trouble-shootingEndress+Hauser 819.4 Spare parts!Note!Installation instructions are included with the spare part.9.4.1 Spare parts diag
9 Trouble-shooting Memo-Graph S82 Endress+Hauser9.4.2 Spare parts listPos. Order No. HOUSING AND HOUSING PARTS1 50084747 Casing without front bezel2 R
Memo-Graph S 9 Trouble-shootingEndress+Hauser 8314 RSG12X-EE PROFIBUS DP interface module 93.75kBit/s,until device no. 4454204114 RSG12X-EF PROFIBUS D
9 Trouble-shooting Memo-Graph S84 Endress+Hauser9.5 Repairs/returnThe device must be packed in protective packaging for later reuse or in case of repa
Memo-Graph S 10 Technical dataEndress+Hauser 8510 Technical data10.1 Function and system designMeasuring principle Electronic acquisition, recording a
10 Technical data Memo-Graph S86 Endress+HauserDigital inputs 10.2.2 Digital I/O board (socket 1, socket 2)15 digital inputsas per DIN 19240: Logic “0
Memo-Graph S 10 Technical dataEndress+Hauser 8710.3 Output values10.3.1 Multifunction output board (socket 2)Analogue outputs 4 or 8 analogue outputs,
10 Technical data Memo-Graph S88 Endress+HauserGiven that this is an interface for industrial use, a screened cable (CAT5) must be used.If a PC is to
Memo-Graph S 10 Technical dataEndress+Hauser 89Ingress protection class Front ingress protection: for die-cast front with door: IP 54 (EN 60529, Cat.
Memo-Graph S 2 IdentificationEndress+Hauser 92 Identification2.1 Device designation2.1.1 NameplateCompare the nameplate on the device with the deliver
10 Technical data Memo-Graph S90 Endress+HauserPanel mounting dimensions for version with IP 65 stainless steel front and rear panel or terminal cover
Memo-Graph S 10 Technical dataEndress+Hauser 91Field housing IP65 field housing dimensions:Figure 13: Field housing dimensionsWeight VDM with front in
10.9 Data storageSelectable memory cycle per group (standard or event storage)1s/2s/3s/5s/10s/15s/30s/1min/2min/3min/6min >= 4 year buffering for p
Memo-Graph S 10 Technical dataEndress+Hauser 9310.10 Certificates and approvalsCE mark The measuring system meets the legal requirements of the EC dir
Index Memo-Graph S95IndexSymbols"Extras" key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71"Group" key
Memo-Graph S Index96Last power on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54LCD running time . . . . . . . . . . . . .
Index Memo-Graph S97Working temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 88ZZero reset . . . . . . . . . . . . . . . . . . .
www.endress.com/worldwideBA 138R/09/en/08.0451006049FM+SGML 6.0