5 Operation / adjusting device settings - Set-up to commissioning Memo-Graph S
56 Endress+Hauser
5.9 Communication via serial interfaces / modem
5.9.1 RS 232
The RS 232 serial interface can be accessed from the front (3.5 mm stereo jack plug under the ATA
flash drive) (not available for stainless steel front) and from the rear (9 pin Sub-D socket).
"
Caution!
• Simultaneously using the front and the rear-mounted RS 232 is not permitted. Device malfunc-
tion.
Only the front-mounted interface with die-cast front (IP 54) with a door can be accessed, and not
the version with stainless steel front.
5.9.2 RS 485
This interface (option) can be accessed alternatively at the rear side interface. The RS 485 can be
used for remote configuration/readout (up to approx. 1000 m lead length).
"
Caution!
When using an RS 232 / RS 485 converter, ensure that it supports automatic change over between
sending and receiving (e.g. W+T type 86000).
5.9.3 PROFIBUS DP
When connecting to PROFIBUS DP, you can display, record and monitor measured values. These
measuring points are treated as conventionally-wired analogue signals.
Both PROFIBUS DP and conventionally-connected measuring points can be used simultaneously
with one device, since the input signal for each channel is selected separately. A total of up to 16
measuring points are available per device (plus the digital inputs and mathematics channels).
“Monitor” operating mode:
A master (e.g. existing control system) interrogates the connected slaves without affecting the sys-
tem itself. Physically, the RS 485 interface is used (Baudrate 93.750 kBit/s, alternatively 45.45
kBaud, fixed).
The measurement data from the slaves is analysed. For this, the slave address and data format setting
is required for each channel (see “Set-up - Analogue inputs - Channel xx - PROFIBUS DP”).
Please refer to your transmitter's specifications/data here. If a slave delivers several measured data
sets (multiparameter transmitter/“modular slave”), each set of information requires its own chan-
nel.
!
Note!
In order to be displayed correctly, the true, physical measured values (e.g. in °C, bar...) must be
transferred. Scaling at the device is not possible.
• Please ensure that connections that are not used are also not switched on at the plug.
• PROFIBUS PA devices can be used via the PA/DP bus coupler (“Segment coupler”).
PROFIBUS measuring points can be calculated with each other and with conventionally connec-
ted analogue measuring points in mathematics module.
“Slave” operating mode:
Slave functions in combination with Profibus coupler (Accessories: RSG12A-P1). Insert for bi-direc-
tional communication in cyclic data transfer.
Baudrate: max. 12 Mbaud, adjustable.